Surge Protection Monitoring

ProALARM II

Raycap ProAlarm II is a DIN rail-type fault indicator device that notifies the user when an end-of-life Surge Protective Device (SPD) needs to be replaced. It connects to the SPD's remote contact (RC) and is mounted next to it on the same rail. When the SPD fails, it alerts the user with a loud warning signal and a red LED. The alarm can be silenced with a button; the LED remains lit until the SPD is replaced. Multiple SPDs can be connected to a single ProAlarm II.

Surge Protective Devices (SPDs) fail silently. The system continues to operate, with no indication — but protection is gone. In the next lightning strike or surge, damage directly reaches the equipment. Therefore, detecting the failure status of the SPD is as critical as the protection itself.

ProAlarm II fills this gap. The device is quickly and easily mounted on the same DIN rail, right next to the SPD, by connecting the SPD's remote signaling contact (RC) to the alarm unit. No separate panel, additional power line, or complex wiring is required.

When an SPD fails, the user is notified in two different ways:

  • Loud beep — 70 dB sound power level
  • Red LED — visual indicator

The alarm can be silenced with the button on the device. However, the LED remains lit — until the SPD is actually replaced. This design choice is important: once acknowledged, the audible warning does not disturb, but the resolution of the fault is not forgotten.

Multiple SPDs can be connected to a single ProAlarm II — all SPDs in the panel can be aggregated onto one alarm unit. The maximum connection distance is 50 m.

The device operates at a rated voltage of 110–230 V AC, supporting a frequency range of 50–60 Hz. It draws 0 mA current in normal operation; it consumes 10–21 mA only when alarming. It is only 1 TE / 18 mm wide and weighs 53 g.

The product complies with IEC 61010-1:2010+A1:2016 and EN 61010-1:2010+A1:2019 standards; it is RoHS and CE certified.

  • SPD fault notification with audible alarm
  • Visual SPD fault notification with red LED
  • Acknowledge and silence button for the alarm — LED remains lit
  • Multiple SPDs can be connected to a single ProAlarm II
  • Rated voltage AC 110 – 230 V
  • Simple connection to the SPD's remote contact (RC)
  • Quick and easy mounting next to the SPD on the same DIN rail
  • Maximum connection distance: 50 m
  • 0 mA current consumption in normal operation
  • Sound power level: 70 dB
  • Compact size: 1 TE / 18 mm
  • 35 mm DIN rail mounting (EN 60715)
  • Protection class: IP 20
  • Housing: UL 94 V-0 flame retardant thermoplastic
  • Overvoltage category: III
  • Operating temperature: -20 °C … +70 °C
  • Standards: IEC 61010-1:2010+A1:2016, EN 61010-1:2010+A1:2019
  • Certifications: RoHS, CE

Technical data

ProAlarm II
Order code 130 562
Rated voltage (AC) 110 – 230 V
Rated frequency 50 – 60 Hz
Rated current 0 mA
Rated current (when alarming) 10 mA (110 V) / 21 mA (230 V)
Overcurrent protection (max.) 16 A
RC rated current 10 mA (110 V) / 21 mA (230 V)
TOV withstand 120 min ⁽¹⁾ 442 V
Max. discharge current Imax (8/20 µs) ⁽¹⁾⁽²⁾ 50 kA
Impulse discharge current Iimp (10/350 µs) ⁽¹⁾⁽³⁾ 12.5 kA
Overvoltage category III
Mounting 35 mm DIN rail (EN 60715)
Operating temperature -20 °C … +70 °C
Housing material Thermoplastic, UL 94 V-0
Protection class IP 20
Indication Red LED / audible alarm
Sound power level LWA 70 dB
Dimensions DIN 43880 1 TE (18 mm)
Packaging dimensions 77.8 × 23 × 108 mm
Weight 53 g

ProAlarm II is used for fault notification in panels with remote contact SPDs:

  • LV distribution boards — SPD fault notification
  • Main and sub-distribution boards — Central alarm point
  • SPDs with remote contact (-R) — RC output evaluation
  • Facilities without monitoring systems — On-site alarm instead of SCADA/PLC
  • Facilities with personnel — Immediate detection with audible warning
  • Panels with numerous SPDs — Collective notification on a single unit
  • Solar power plants (GES) — DC and AC side SPD monitoring
  • Industrial facilities — Factory and production panels
  • Commercial buildings — Office, shopping mall, hotel electrical panels
  • Critical infrastructure facilities — Hospital, data center, telecom
  • Periodic maintenance programs — Determining replacement time
  • Facilities where undetected loss of protection is unacceptable
  • Distributed panel layouts up to 50 m — Single-point alarm from remote panels