Data and Signal Line Surge Protection

Telecommunication and DSL Protection

The Raycap RayTel and RayDat telecommunication protection family protects subscriber telephone and DSL lines against lightning, switching, and mains-induced overvoltages. With a high frequency range up to 250 MHz, it is suitable for all DSL lines; it supports ADSL, ADSL2, and ADSL2+ protocols over POTS and ISDN lines. Wall or DIN rail mounting versions are offered with screw, quick-connect, or RJ45 terminal options.

Data transmission is an integral part of daily life — therefore, providing adequate protection for this type of signal is crucial. Whether at the building entrance or for telephone connections within the home or office, these solutions should be considered part of the building's lightning protection system.

These SPDs protect subscriber telecommunication equipment against lightning strikes, switching operations, and surges from the telecommunication network.

Complete protection on the telecommunication side fully supports signal transmission of DSL technologies even in systems with excessively long cable routes. Within the operating frequency range, operational degradation and insertion loss are negligible. The protection module is adapted to the frequency characteristics of the subscriber's twisted pair cable — the same module can be used on ADSL, ADSL2, and ADSL2+ protocols, over both POTS and ISDN lines.

Product families:

RayTel 10 — Compact, telecommunication-side protection with RJ11 or RJ45 connection. Up to 175 V DC. Thyristor surge suppressor + GDT + thermo-clip structure. Frequency range up to 10 MHz. Can be connected directly to the telephone socket.

RayTel 20 — High-performance model for DSL networks. Bandwidth up to 250 MHz — highest in the family. 20 kA total discharge current and 7.5 kA total lightning impulse current (10/350 µs). Suitable for outdoor and building entrance installation with IP66 protection class and polypropylene housing.

RayDat SPH-2-230 / SPH-4-230 — For high-voltage lines up to 230 V DC. MOV + GDT structure, 5 A load current.

RayDat SLH-2-110 / SLH-4-110 — 110 V DC standard modular protection. Single pair (SLH-2) and two-pair (SLH-4) versions.

RayDat SUI-4-110 — High-capacity model for exposed lines. In 20 kA, Imax 30 kA — highest discharge values in the family.

RayDat SRH-2-110 — Version with remote signal contact. Contact changes position in case of fault; information is transmitted to the monitoring system.

RayDat SGH-3-110 — For systems requiring separated signal ground, especially RS 232.

Technical approach: Devices have a multi-stage structure — coarse protection is provided by a gas discharge tube (GDT), fine protection by a diode block (SAD). The series resistance (1.6–2.0 Ω) between them establishes energy coordination. The thermo-clip eliminates the risk of fire and shock by diverting current to ground in case of mains incursion between the power line and the communication line.

Products comply with IEC/EN 61643-21 standard. Classification: D1 / C1 / C2 / C3.

Common features

  • Very high impulse withstand values
  • Screw, quick-connect (spring), or RJ45 terminal options
  • Wall mount or DIN rail mount versions
  • High frequency range up to 250 MHz — suitable for all DSL lines
  • ADSL, ADSL2, ADSL2+ protocols — over POTS and ISDN lines
  • Full signal transmission even on excessively long cable routes
  • Negligible insertion loss
  • Multi-stage hybrid protection: GDT (coarse) + diode block / thyristor (fine)
  • Thermo-clip — mains incursion protection
  • Energy coordination between stages
  • Protection class: IP 20 (RayTel 20: IP 66)
  • Housing: gray thermoplastic, V-0 flame resistance
  • Operating temperature: -40 °C … +80 °C
  • Classification: D1 / C1 / C2 / C3
  • Standard: IEC/EN 61643-21

RayTel 10 (compact, RJ11/RJ45)

RayTel 10
Max. continuous operating voltage Uc 175 V DC
Max. operating current IL 150 mA
In (8/20 µs) a/b-PE, a-b 2.5 kA
Imax (8/20 µs) 5 kA
Protection level Up (a-b) ≤ 300 V
Protection level Up (a/b-PE) ≤ 1000 V
Series resistance R 0.2 – 0.4 Ω
Series inductance L 2 × 25 µH
Capacitance C < 100 pF
Frequency range fG up to 10 MHz
Response time tA (a-b / a,b-PE) < 5 ns / < 100 ns
Connection RJ11 or RJ45
Temperature -40 °C … +60 °C
Weight 70 g
Order code 124 150

RayTel 20 (DSL, high performance, IP66)

RayTel 20
Protected pair 1 pair (2 conductors)
Nominal operating voltage Un 110 V DC
Max. continuous operating voltage (DC / AC) Uc 180 V / 127 V
Nominal current IL (40 °C) 0.6 A
C2 total discharge current In (8/20 µs) 20 kA
C2 In per line 10 kA
D1 total lightning impulse current Iimp (10/350 µs) 7.5 kA
D1 Iimp per line 2.5 kA
Protection level Up (line-line / lines-ground) < 250 V / < 550 V
Series resistance RS 1.6 – 2.0 Ω
Bandwidth fG up to 250 MHz
Capacitance (line-line / lines-ground) ≤ 20 pF / ≤ 10 pF
Protection class IP 66
Housing Polypropylene, gray
Temperature -25 °C … +80 °C
Weight 150 g
Order code 124 152

RayDat modular series comparison

Model Protected line Un Uc In Imax Iimp Ures @5 kA fG Feature
SPH-2-230 1 pair 230 V 320 V 10 kA 20 kA 2.5 kA < 700 V 10 MHz 5 A load current, MOV+GDT
SLH-2-110 1 pair 110 V 170 V 10 kA 20 kA 2.5 kA < 450 V 30 MHz Standard
SLH-4-110 2 pairs 110 V 170 V 10 kA 20 kA 5 kA < 450 V 30 MHz Two pairs
SUI-4-110 2 pairs 110 V 170 V 20 kA 30 kA 5 kA < 450 V 30 MHz Exposed lines
SRH-2-110 1 pair 110 V 170 V 10 kA 20 kA 2.5 kA < 450 V 30 MHz Remote contact
SGH-3-110 1 pair 110 V 170 V 10 kA 20 kA 2.5 kA < 450 V 30 MHz Separated signal ground

The RayTel and RayDat telecommunication series is used for the protection of telephone and broadband lines:

  • Building entrance telecom lines — As part of the lightning protection system
  • DSL modem and router inputs — ADSL, ADSL2, ADSL2+ lines
  • POTS (analog telephone) lines — Subscriber telephone connection
  • ISDN lines — Digital subscriber lines
  • Home and office telephone sockets — Direct connection with RJ11/RJ45 (RayTel 10)
  • Outdoor and field cabinets — With IP66 housing (RayTel 20)
  • Exchanges and distribution points — Subscriber line aggregation points
  • Telecom lines running through open areas — High-capacity protection (SUI-4-110)
  • 230 V DC signal lines — High-voltage circuits (SPH-2-230)
  • RS 232 connections — Systems requiring separated signal ground (SGH-3-110)
  • Remotely monitored facilities — Transmission of fault information to the center (SRH-2-110)
  • Excessively long cable routes — Lines where signal quality must be maintained
  • Alarm and security systems — Communication via telephone line
  • High lightning risk areas — Against mains-induced surges
  • Surge Protection Catalog 2021 for Data Signal Line Systems Download
  • Telecommunication and DSL Signal Data Sheets Download