Data and Signal Line Surge Protection

Analog Signal Protection – RayDat Series

The Raycap RayDat analog signal protection series is a modular SPD family developed for the protection of measurement, control, and communication circuits against lightning-induced surges. With its GDT (coarse protection) + SAD (fine protection) hybrid structure, it provides both common mode and differential mode protection. Key features include high density up to 4 lines in 12 mm width, uninterrupted line connection during module replacement, and ATEX/IECEx certified Ex versions.

Analog signal lines — 4-20 mA loops, sensor cables, measurement, and control circuits — often cover long distances and pass through open areas. These lines are vulnerable to lightning-induced surges; damage to a transmitter or PLC input card leads to production loss far exceeding the cost of the device.

The RayDat series is a modular SPD family designed for the protection of these lines. The devices feature a multi-stage structure:

  • Coarse protection stage: A three-pole gas discharge tube (GDT) that diverts primary impulse energy to ground.
  • Fine protection stage: A fast bidirectional silicon avalanche diode (SAD) that reduces residual voltage to a level tolerable by sensitive electronics.

The fine protection stage is designed to avoid capacitive line loading — meaning low insertion loss and a wide operating frequency range (up to 30 MHz). Series line impedances between stages ensure energy coordination between the two stages at every impulse level; no voltage or impulse current "blind spots" occur.

The decisive safety element of the series is the thermo-clip. When a mains frequency contact occurs between the power line and the communication line ("mains incursion"), this creates a risk of electric shock and fire. The thermo-clip in the primary protection stage eliminates this risk by diverting the mains frequency current to ground.

Thanks to the pluggable module/base design, an end-of-life module can be replaced without disconnecting system wiring. The critical point is: when the module is removed from the base, the connection lines remain active — meaning replacing the protection module does not interrupt production or communication.

The products comply with IEC/EN 61643-21 and UL 497B 4th Edition standards; many models are UL Listed. Classification: D1 / C1 / C2 / C3. 35 mm DIN rail mounted, available with screw or quick-connect (spring) terminals.

Product families:

  • RayDat SL Series — Basic modular protection. SLH-2 (single pair), SLH-4 (two pairs), SSH-3 (shielded cable), SLL-4 (fine protection only), SUI-4 (high capacity for open lines)
  • RayDat SRH Series — Version with remote signal contact. The contact changes position in case of failure. The SRH-2L model also features an LED visual indicator.
  • RayDat SP Series — For ungrounded double loops. Designed for sites with high ground potential rise, such as near electric railways. SPH-2, SPH-4, SPI-2, SPI-4.
  • RayDat Ex Series — ATEX/IECEx certified versions for explosive atmospheres. Ex-2 (DIN rail) and PLP Ex family (stainless steel, IP54, with conduit connection).

Common features

  • Multi-stage hybrid protection: GDT (coarse) + SAD (fine)
  • Common mode (longitudinal) and differential mode (transverse) protection
  • Very high impulse withstand values
  • Connection lines remain active during module replacement
  • High density — up to 4 protected lines in only 12 mm width
  • Energy coordination between stages (series line impedance)
  • Thermo-clip — fire and shock protection against mains incursion
  • Low insertion loss, wide frequency range (up to 30 MHz)
  • Screw or quick-connect (spring) terminal options
  • Potential-free contact version for fault detection (SRH series)
  • LED visual fault indicator on some models (SRH-2L)
  • Direct / indirect shield grounding options
  • 35 mm DIN rail mounting (IEC/EN 60715)
  • Housing: gray thermoplastic, V-0 flame resistance
  • Protection class: IP 20 (embedded)
  • Operating temperature: -40 °C … +80 °C
  • Classification: D1 / C1 / C2 / C3
  • Standards: IEC/EN 61643-21, UL 497B 4th Edition

Model comparison — RayDat SL Series

Model Protected line In (8/20 µs) Imax (8/20 µs) Iimp (10/350 µs) Voltage (V DC)
SLH-2 1 pair (2 conductors) 10 kA 20 kA 2.5 kA 5, 12, 15, 24, 30, 48, 60
SLH-4 2 pairs (4 conductors) 10 kA 20 kA 5 kA 5, 12, 15, 24, 30, 48, 60
SSH-3 (shielded cable) 1 pair (2 conductors) 10 kA 20 kA 2.5 kA 5, 12, 15, 24, 30, 48, 60
SLL-4 (fine protection only) 2 pairs (4 conductors) 250 A 30
SUI-4 (open lines) 2 pairs (4 conductors) 20 kA 30 kA 5 kA 5, 12, 15, 24, 30, 48, 60

Model comparison — RayDat SRH and SP Series

Model Protected line In Imax Iimp Voltage Feature
SRH-2 1 pair 10 kA 20 kA 2.5 kA 5–60 V Remote contact
SRH-2L 1 pair 10 kA 20 kA 2.5 kA 5, 12, 24, 30 V Remote contact + LED
SPH-2 1 pair 10 kA 20 kA 2.5 kA 30 V Ungrounded loop
SPH-4 2 pairs 10 kA 20 kA 5 kA 30 V Ungrounded loop
SPI-2 1 pair 10 kA 20 kA 2.5 kA (total 5 kA) 30 V Ungrounded loop
SPI-4 2 pairs 10 kA 20 kA 2.5 kA (total 10 kA) 30 V Ungrounded loop

Remote contact ratings: AC 250 V/0.5 A — DC 50 V/1 A

Typical electrical values (SLH-2 example)

5 12 15 24 30 48 60
Nominal operating voltage Un 5 V 12 V 15 V 24 V 30 V 48 V 60 V
Max. continuous operating voltage Uc 6 V 15 V 18 V 28 V 33 V 52 V 64 V
Residual voltage @5 kA Ures < 22 V < 42 V < 48 V < 70 V < 80 V < 140 V < 160 V
Insulation resistance Riso ≥ 6 kΩ ≥ 15 MΩ ≥ 18 MΩ ≥ 28 MΩ ≥ 33 MΩ ≥ 52 MΩ ≥ 64 MΩ
  • Rated load current IL: 1 A (25 °C) — SLL-4 and SPH-4-30/0: 10 A
  • Response time tA: < 1 ns (line-line, line-ground)
  • Series resistance R per path: 1.6 – 2.0 Ω (SLL-4: 0.1 Ω)
  • Transverse capacitance C: 50 pF (shield-ground: 5 pF)
  • Cut-off frequency fG: 30 MHz
  • Terminal cross-section: max. 4 mm² (Q version 2.5 mm²)
  • Dimensions: 12 mm width, DIN 43880 2/3 TE — Weight: 52–70 g

RayDat Ex Series — Explosive atmospheres

Ex-2 PLP Ex family
Mounting 35 mm DIN rail Conduit connection (1/2" NPT, M20×1.5, G 1/2")
Housing Thermoplastic, IP 20 Stainless steel, IP 54
Voltage 12, 24 V DC 24, 48, 24/5 V DC
In (8/20 µs) 5 kA 5–10 kA
Imax (8/20 µs) 10 kA 10–20 kA
Iimp (10/350 µs) 1 kA 1.0–2.0 kA
Ex class II 1G Ex ia IIC T* Ga Ex ia IIC T6 Ga / Ex ia IIIC T85 °C Da
Temperature -40 °C … (according to temperature class) -30 °C … +60 °C
Standards IEC/EN 60079-0, 60079-11 + UL 60079-0/-11, CAN/CSA C22.2
  • Ex-2 intrinsic safety: Ui 16/29 V, Ii 500 mA, Pi 2 W, Ci 10 nF, Li 0.11 mH
  • PLP Ex intrinsic safety: Ui 50 V, Ii 800 mA, Pi 2 W, Li 60 µH

The RayDat analog signal protection series is used in signal lines of measurement and control infrastructure:

  • 4-20 mA current loop lines — between field instrument and control system
  • Pressure, temperature, level, and flow transmitters — field measurement devices
  • PLC / DCS analog input-output cards — control system side
  • Instrumentation and marshalling panels — signal collection points
  • Shielded signal cables — including shield protection with SSH-3 series
  • Explosive atmospheres (ATEX/IECEx) — petrochemical, refinery, gas facilities (Ex series)
  • Facilities near electric railways — high ground potential rise (SP series)
  • Ungrounded double loops — SP series
  • Long signal lines passing through open areas — high-capacity protection with SUI-4
  • Remotely monitored facilities — fault information transfer to SCADA with SRH series
  • Water and wastewater facilities — remote pump station instrumentation
  • Power plants and substations — measurement and control circuits
  • Panels with space constraints — 4-line protection in 12 mm width
  • Facilities requiring continuous operation — line remains active during module replacement
  • Data Signal Line Systems Surge Protection Catalog 2021 Download