Data and Signal Line Surge Protection

DC Power Systems – Narrow Line

The Raycap RayDat Narrow Line DC power series (NPS-2) protects DC supply lines in protocols requiring combined power and signal line protection, such as CAN bus and DeviceNet. With its ultra-compact 6.2 mm width, it provides maximum density within the panel; it carries up to 12 A load current, can be used in AC and DC systems, and offers uninterrupted maintenance with hot-swapping support.

In some industrial communication protocols, power and signal are carried within the same cable. CAN bus and DeviceNet are typical examples: the same cable contains both data lines and a DC power line that supplies the devices. In this architecture, protecting the signal line alone is not enough — a surge from the power supply line will also shut down the entire segment.

The RayDat Narrow Line DC series (NPS-2) was developed specifically for the protection of these power lines. By using it side-by-side on the same rail with analog and digital Narrow Line modules, both the signal and power sides of a CAN/DeviceNet segment are fully protected.

The most distinctive feature of the series is its 6.2 mm width — less than half the width of classic modules. In automation panels with numerous nodes, this is a direct advantage reflected in the number of panels.

The device carries a 12 A load current (at 40 °C) — one of the highest values in the Narrow Line family. The series resistance per path is only 0.1 Ω, meaning it does not create a significant voltage drop in the supply line. It can be used in both AC and DC systems (Uc 38 V AC/DC).

The protection structure is a MOV (varistor) + GDT (gas discharge tube) combination: MOV operates line-to-line, GDT operates line-to-ground. The protection level is 250 V line-to-line and 650 V line-to-ground. The response time is < 25 ns. Thermal protection is included.

Hot-swapping capability is critical: when the protection module is removed from the base, the connection lines remain active — module replacement does not stop the bus segment. The green flag / red flag indicator on the front panel instantly shows the status. Additionally, a monitoring unit (transmitter and receiver) is available for all product variants.

Quick-connect terminals shorten field installation time. The product complies with IEC/EN 61643-21 and UL 497B 4th Edition standards. Classification: C1 / C2 / C3.

  • Narrow form factor — only 6.2 mm width
  • High surge withstand values
  • Suitable for AC and DC power systems
  • Hot-swapping — connection lines remain active during module replacement
  • Quick-connect terminals
  • Up to 12 A load current (40 °C) / 10 A (70 °C)
  • For protocols requiring power + signal protection — CAN bus, DeviceNet
  • Protection structure: MOV (line-to-line) + GDT (line-to-ground)
  • Very low series resistance: 0.1 Ω
  • Response time: < 25 ns
  • Thermal protection
  • Status indicator: green flag / red flag
  • Monitoring unit available for all variants (transmitter + receiver)
  • 35 mm DIN rail mounting (IEC/EN 60715)
  • Protection class: IP 20 (embedded)
  • Housing: gray thermoplastic, V-0 flame resistance
  • Operating temperature: -40 °C … +80 °C
  • Classification: C1 / C2 / C3
  • Standards: IEC/EN 61643-21, UL 497B 4th Edition

RayDat NPS-2 Series — Electrical Values

NPS-2-24
Protected line 1 pair (2 conductors)
Nominal operating voltage (DC) Un 24 V
Max. continuous operating voltage (DC) Uc 38 V
Max. continuous operating voltage (AC) Uc 38 V
Nominal load current IL (40 °C) 12 A
Nominal load current IL (70 °C) 10 A
C2 In (8/20 µs) line-to-line 4 kV / 2 kA
C2 In (8/20 µs) line-to-ground 4 kV / 2 kA
C2 total In (8/20 µs) 8 kV / 4 kA
C2 protection level Up (line-to-line) 250 V
C2 protection level Up (line-to-ground) 650 V
C3 protection level Up (line-to-line) 200 V
C3 protection level Up (line-to-ground) 700 V
Nominal sparkover voltage (line-to-line) 84 – 106 V
Nominal sparkover voltage (line-to-ground) 72 – 160 V
Response time tA < 25 ns
Thermal protection Yes
Insulation resistance (line-to-line) Riso > 10 MΩ
Series resistance per path R 0.1 Ω
Capacitance (line-to-line / line-to-ground) typ. 5 nF / 10 pF
Max. frequency fG 550 kHz (up to 800 kHz)

Mechanical

  • Dimensions: 6.2 mm width (DIN 43880) — Weight: 58 g (module: 16 g)
  • Conductor cross-section (max.): 4 mm² (solid) / 2.5 mm² (flexible)
  • Mounting: 35 mm DIN rail (IEC/EN 60715)
  • Packaging: 113 × 111 × 11 mm — Min. package quantity: 15

RayDat Narrow Line DC power series is used in supply lines of systems where power and signal are carried together:

  • CAN bus networks — Segments carrying power + signal in the same cable
  • DeviceNet networks — Industrial device-level communication
  • 24 V DC supply lines — Sensor, actuator, and field device power supplies
  • Automation panels — Facilities with numerous nodes
  • Space-critical panels — Maximum density with 6.2 mm width
  • High-current supply lines — Up to 12 A load current
  • AC and DC mixed systems — Up to 38 V AC/DC
  • PLC and controller supply outputs — Control system side
  • Field device power distribution — Marshalling panels
  • With Narrow Line analog/digital modules — Complete segment protection on the same rail
  • Facilities requiring continuous operation — Maintenance without bus interruption via hot-swapping
  • Remotely monitored facilities — SCADA integration with monitoring unit (transmitter/receiver)
  • Projects requiring fast commissioning — Short installation time with quick-connect terminals
  • Harsh industrial environments — -40 °C … +80 °C operating range