{"id":56453,"date":"2020-11-15T12:58:37","date_gmt":"2020-11-15T09:58:37","guid":{"rendered":"https:\/\/yilkomer.com\/topraklama-uygulamalarinda-dogrular-ve-yanlislar\/"},"modified":"2026-01-19T17:35:02","modified_gmt":"2026-01-19T14:35:02","slug":"correct-and-incorrect-practices-in-grounding-applications","status":"publish","type":"post","link":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/","title":{"rendered":"Correct and Incorrect Practices in Grounding Applications"},"content":{"rendered":"<p>Unfortunately, incorrect information that is thought to be correct in grounding practices still appears in current applications. With this article, we wanted to explain some important points that raise questions about grounding.<\/p>\n<p>As Y\u0131lkomer, we will continue to provide you with up-to-date information on low voltage surge protection systems, grounding, equipotential bonding, and lightning protection through short and informative texts.<\/p>\n<p>We hope that the items summarized below will be beneficial for your applications.<\/p>\n<ul>\n<li>The use of rod-type grounding electrodes is not the only alternative in grounding applications; successful results can also be achieved with applications made using mesh and plate methods<\/li>\n<li>In grounding applications, implementations based on touch voltage are technically more correct. Compliance of only the spreading resistance should not be taken as the basis.<\/li>\n<li>If rod-type grounding electrodes are used in grounding applications, the distance between the rods should be at least more than 2 times the rod length.<\/li>\n<li>If a ring-shaped grounding electrode and a rod electrode are used simultaneously, the rod should be located at a distance equal to 5 times the side length of the ring opposite it.<\/li>\n<li>In TT system grounding types, the use of a residual current device is mandatory. Facilities where it is thought not to be mandatory and where no Residual Current Device is used are not compliant with regulations.<\/li>\n<li>All consumers receiving Low Voltage energy from energy supply organizations must use a TT Type grounding system<\/li>\n<li>While a target grounding value is sought in facilities using classical varistor-based surge protectors, no target grounding value is required in surge protection systems using Strikesorb technology.<\/li>\n<li>In grounding systems, if rod, ring, and mesh-type electrodes are used together, calculating the resistance of each and assuming they operate in parallel to find an equivalent parallel resistance leads to incorrect results.<\/li>\n<li>In grounding application and calculations, the soil resistivity value must be measured.<\/li>\n<li>In workplaces, it is observed that separate groundings are requested for different systems such as UPS, servers, computers, and low current systems. If there are different grounding systems in a building, a fault occurring in one will create dangerous voltages between these two systems. Therefore, all groundings must be equipotential.<\/li>\n<\/ul>\n<p style=\"text-align: center;\"><img loading=\"lazy\" decoding=\"async\" class=\"alignnone wp-image-14367 size-large\" src=\"https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/topraklama-yanlislari-scaled.jpg\" alt=\"topraklama yanli\u015f uygulamalar\u0131\" width=\"681\" height=\"1024\" srcset=\"https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/topraklama-yanlislari-scaled.jpg 1702w, https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/topraklama-yanlislari-scaled-199x300.jpg 199w, https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/topraklama-yanlislari-scaled-681x1024.jpg 681w, https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/topraklama-yanlislari-scaled-768x1155.jpg 768w, https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/topraklama-yanlislari-scaled-1021x1536.jpg 1021w, https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/topraklama-yanlislari-scaled-1362x2048.jpg 1362w, https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/topraklama-yanlislari-scaled-97x146.jpg 97w, https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/topraklama-yanlislari-scaled-33x50.jpg 33w, https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/topraklama-yanlislari-scaled-50x75.jpg 50w, https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/topraklama-yanlislari-scaled-479x720.jpg 479w, https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/topraklama-yanlislari-scaled-600x902.jpg 600w\" sizes=\"auto, (max-width:767px) 480px, 681px\" \/><\/p>\n<ul>\n<li>The voltages occurring between neutral lines and grounding lines are not directly related to poor building grounding. The value read is the voltage drop on the neutral lines. It is not possible to reduce this value by adding additional grounding. In LV installations, trying to find a solution by grounding the neutral line with a separate electrode is hazardous. With this application, operational grounding is added to the network neutral. The proximity of this grounding to the building grounding (20m) is also hazardous.<\/li>\n<li>Lightning protection grounding must definitely be included in equipotential bonding. System grounding and lightning protection grounding must not be separate.<\/li>\n<li>In grounding applications, it is not mandatory to use only copper conductors and electrodes; galvanized grounding conductors can also be used in grounding applications. The use of aluminum-based conductors in grounding applications is not appropriate.<\/li>\n<li>Using different types of metals together in grounding applications is not appropriate. Using copper and galvanized conductors together causes a bimetal effect.<\/li>\n<li>The use of anti-corrosion tape at connection points in grounding applications provides a preventive effect against possible corrosion and increases in resistance<\/li>\n<li>The suitability of resistance values that activate protective devices is more important than the grounding resistance value itself. For example, if a facility grounding measures 1 ohm, it has no significance. What matters is whether the protective grounding operates within the system.<\/li>\n<li>Connecting lightning protection equipment to foundation grounding branches depends on certain conditions. Without performing a continuity test and without using Type 1+2 surge protectors throughout the building, this application is not appropriate.<\/li>\n<\/ul>\n<p> You can always receive support from Y\u0131lkomer on grounding project design, equipment supply, application, and measurement.<\/p>\n<p>Do not forget, Y\u0131lkomer \u2018Protects Your Values!\u2019<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Unfortunately, incorrect information that is thought to be correct in grounding practices still appears in current applications. With this article, we wanted to explain some important<span class=\"excerpt-hellip\"> [\u2026]<\/span><\/p>\n","protected":false},"author":1,"featured_media":56454,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_joinchat":[],"footnotes":""},"categories":[193],"tags":[],"class_list":["post-56453","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-general"],"yoast_head":"<!-- This site is optimized with the Yoast SEO Premium plugin v19.2.1 (Yoast SEO v27.4) - https:\/\/yoast.com\/product\/yoast-seo-premium-wordpress\/ -->\n<title>Correct and Incorrect Practices in Grounding Applications | Y\u0131lkomer<\/title>\n<meta name=\"description\" content=\"We have written for you the correct and incorrect practices in grounding applications; click now to read the commonly known misconceptions...\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Correct and Incorrect Practices in Grounding Applications\" \/>\n<meta property=\"og:description\" content=\"Unfortunately, incorrect information that is thought to be correct in grounding practices still appears in current applications. With this article, we\" \/>\n<meta property=\"og:url\" content=\"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/\" \/>\n<meta property=\"og:site_name\" content=\"Y\u0131lkomer\" \/>\n<meta property=\"article:author\" content=\"https:\/\/www.facebook.com\/yilkomer\" \/>\n<meta property=\"article:published_time\" content=\"2020-11-15T09:58:37+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2026-01-19T14:35:02+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/Topraklama-uygulamalarinda-sikca-yapilan-yanlislar.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"1280\" \/>\n\t<meta property=\"og:image:height\" content=\"720\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\n<meta name=\"author\" content=\"Y\u0131ld\u0131r\u0131mdan Korunma Merkezi\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Y\u0131ld\u0131r\u0131mdan Korunma Merkezi\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"4 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/\"},\"author\":{\"name\":\"Y\u0131ld\u0131r\u0131mdan Korunma Merkezi\",\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/#\\\/schema\\\/person\\\/1378732ec91a59af36092fedd9f6f871\"},\"headline\":\"Correct and Incorrect Practices in Grounding Applications\",\"datePublished\":\"2020-11-15T09:58:37+00:00\",\"dateModified\":\"2026-01-19T14:35:02+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/\"},\"wordCount\":643,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/#organization\"},\"image\":{\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/yilkomer.com\\\/wp-content\\\/uploads\\\/2020\\\/11\\\/Topraklama-uygulamalarinda-sikca-yapilan-yanlislar.jpg\",\"articleSection\":[\"General\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/\",\"url\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/\",\"name\":\"Correct and Incorrect Practices in Grounding Applications | Y\u0131lkomer\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/yilkomer.com\\\/wp-content\\\/uploads\\\/2020\\\/11\\\/Topraklama-uygulamalarinda-sikca-yapilan-yanlislar.jpg\",\"datePublished\":\"2020-11-15T09:58:37+00:00\",\"dateModified\":\"2026-01-19T14:35:02+00:00\",\"description\":\"We have written for you the correct and incorrect practices in grounding applications; click now to read the commonly known misconceptions...\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/#primaryimage\",\"url\":\"https:\\\/\\\/yilkomer.com\\\/wp-content\\\/uploads\\\/2020\\\/11\\\/Topraklama-uygulamalarinda-sikca-yapilan-yanlislar.jpg\",\"contentUrl\":\"https:\\\/\\\/yilkomer.com\\\/wp-content\\\/uploads\\\/2020\\\/11\\\/Topraklama-uygulamalarinda-sikca-yapilan-yanlislar.jpg\",\"width\":1280,\"height\":720,\"caption\":\"topraklama uygulamas\u0131nda s\u0131k\u00e7a yap\u0131lan yanl\u0131\u015flar\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/correct-and-incorrect-practices-in-grounding-applications\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Ana Sayfa\",\"item\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Correct and Incorrect Practices in Grounding Applications\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/#website\",\"url\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/\",\"name\":\"Y\u0131lkomer\",\"description\":\"\",\"publisher\":{\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/#organization\"},\"alternateName\":\"Y\u0131lkomer\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/#organization\",\"name\":\"Yilkomer\",\"url\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/yilkomer.com\\\/wp-content\\\/uploads\\\/2015\\\/01\\\/logo.png\",\"contentUrl\":\"https:\\\/\\\/yilkomer.com\\\/wp-content\\\/uploads\\\/2015\\\/01\\\/logo.png\",\"width\":1000,\"height\":189,\"caption\":\"Yilkomer\"},\"image\":{\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/#\\\/schema\\\/logo\\\/image\\\/\"}},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/yilkomer.com\\\/en\\\/#\\\/schema\\\/person\\\/1378732ec91a59af36092fedd9f6f871\",\"name\":\"Y\u0131ld\u0131r\u0131mdan Korunma Merkezi\",\"description\":\"Y\u0131lkomer (Y\u0131ld\u0131r\u0131mdan Korunma Merkezi) \u00fclkemizde y\u0131ld\u0131r\u0131mdan ve a\u015f\u0131r\u0131 gerilimden korunmada teknik eksiklikleri ortadan kald\u0131rarak tamamen standartlar ve m\u00fchendislik hesaplar\u0131na dayanarak sistem kurmay\u0131 hedeflemektedir.\",\"sameAs\":[\"https:\\\/\\\/www.facebook.com\\\/yilkomer\",\"https:\\\/\\\/www.linkedin.com\\\/profile\\\/view?id=393173773&trk=nav_responsive_tab_profile\",\"https:\\\/\\\/x.com\\\/https:\\\/\\\/twitter.com\\\/yilkomer\",\"admin\"]}]}<\/script>\n<!-- \/ Yoast SEO Premium plugin. -->","yoast_head_json":{"title":"Correct and Incorrect Practices in Grounding Applications | Y\u0131lkomer","description":"We have written for you the correct and incorrect practices in grounding applications; click now to read the commonly known misconceptions...","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/","og_locale":"en_US","og_type":"article","og_title":"Correct and Incorrect Practices in Grounding Applications","og_description":"Unfortunately, incorrect information that is thought to be correct in grounding practices still appears in current applications. With this article, we","og_url":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/","og_site_name":"Y\u0131lkomer","article_author":"https:\/\/www.facebook.com\/yilkomer","article_published_time":"2020-11-15T09:58:37+00:00","article_modified_time":"2026-01-19T14:35:02+00:00","og_image":[{"width":1280,"height":720,"url":"https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/Topraklama-uygulamalarinda-sikca-yapilan-yanlislar.jpg","type":"image\/jpeg"}],"author":"Y\u0131ld\u0131r\u0131mdan Korunma Merkezi","twitter_misc":{"Written by":"Y\u0131ld\u0131r\u0131mdan Korunma Merkezi","Est. reading time":"4 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/#article","isPartOf":{"@id":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/"},"author":{"name":"Y\u0131ld\u0131r\u0131mdan Korunma Merkezi","@id":"https:\/\/yilkomer.com\/en\/#\/schema\/person\/1378732ec91a59af36092fedd9f6f871"},"headline":"Correct and Incorrect Practices in Grounding Applications","datePublished":"2020-11-15T09:58:37+00:00","dateModified":"2026-01-19T14:35:02+00:00","mainEntityOfPage":{"@id":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/"},"wordCount":643,"commentCount":0,"publisher":{"@id":"https:\/\/yilkomer.com\/en\/#organization"},"image":{"@id":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/#primaryimage"},"thumbnailUrl":"https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/Topraklama-uygulamalarinda-sikca-yapilan-yanlislar.jpg","articleSection":["General"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/","url":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/","name":"Correct and Incorrect Practices in Grounding Applications | Y\u0131lkomer","isPartOf":{"@id":"https:\/\/yilkomer.com\/en\/#website"},"primaryImageOfPage":{"@id":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/#primaryimage"},"image":{"@id":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/#primaryimage"},"thumbnailUrl":"https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/Topraklama-uygulamalarinda-sikca-yapilan-yanlislar.jpg","datePublished":"2020-11-15T09:58:37+00:00","dateModified":"2026-01-19T14:35:02+00:00","description":"We have written for you the correct and incorrect practices in grounding applications; click now to read the commonly known misconceptions...","breadcrumb":{"@id":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/"]}]},{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/#primaryimage","url":"https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/Topraklama-uygulamalarinda-sikca-yapilan-yanlislar.jpg","contentUrl":"https:\/\/yilkomer.com\/wp-content\/uploads\/2020\/11\/Topraklama-uygulamalarinda-sikca-yapilan-yanlislar.jpg","width":1280,"height":720,"caption":"topraklama uygulamas\u0131nda s\u0131k\u00e7a yap\u0131lan yanl\u0131\u015flar"},{"@type":"BreadcrumbList","@id":"https:\/\/yilkomer.com\/en\/correct-and-incorrect-practices-in-grounding-applications\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Ana Sayfa","item":"https:\/\/yilkomer.com\/en\/"},{"@type":"ListItem","position":2,"name":"Correct and Incorrect Practices in Grounding Applications"}]},{"@type":"WebSite","@id":"https:\/\/yilkomer.com\/en\/#website","url":"https:\/\/yilkomer.com\/en\/","name":"Y\u0131lkomer","description":"","publisher":{"@id":"https:\/\/yilkomer.com\/en\/#organization"},"alternateName":"Y\u0131lkomer","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/yilkomer.com\/en\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Organization","@id":"https:\/\/yilkomer.com\/en\/#organization","name":"Yilkomer","url":"https:\/\/yilkomer.com\/en\/","logo":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/yilkomer.com\/en\/#\/schema\/logo\/image\/","url":"https:\/\/yilkomer.com\/wp-content\/uploads\/2015\/01\/logo.png","contentUrl":"https:\/\/yilkomer.com\/wp-content\/uploads\/2015\/01\/logo.png","width":1000,"height":189,"caption":"Yilkomer"},"image":{"@id":"https:\/\/yilkomer.com\/en\/#\/schema\/logo\/image\/"}},{"@type":"Person","@id":"https:\/\/yilkomer.com\/en\/#\/schema\/person\/1378732ec91a59af36092fedd9f6f871","name":"Y\u0131ld\u0131r\u0131mdan Korunma Merkezi","description":"Y\u0131lkomer (Y\u0131ld\u0131r\u0131mdan Korunma Merkezi) \u00fclkemizde y\u0131ld\u0131r\u0131mdan ve a\u015f\u0131r\u0131 gerilimden korunmada teknik eksiklikleri ortadan kald\u0131rarak tamamen standartlar ve m\u00fchendislik hesaplar\u0131na dayanarak sistem kurmay\u0131 hedeflemektedir.","sameAs":["https:\/\/www.facebook.com\/yilkomer","https:\/\/www.linkedin.com\/profile\/view?id=393173773&trk=nav_responsive_tab_profile","https:\/\/x.com\/https:\/\/twitter.com\/yilkomer","admin"]}]}},"_links":{"self":[{"href":"https:\/\/yilkomer.com\/en\/wp-json\/wp\/v2\/posts\/56453","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/yilkomer.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/yilkomer.com\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/yilkomer.com\/en\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/yilkomer.com\/en\/wp-json\/wp\/v2\/comments?post=56453"}],"version-history":[{"count":2,"href":"https:\/\/yilkomer.com\/en\/wp-json\/wp\/v2\/posts\/56453\/revisions"}],"predecessor-version":[{"id":56462,"href":"https:\/\/yilkomer.com\/en\/wp-json\/wp\/v2\/posts\/56453\/revisions\/56462"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/yilkomer.com\/en\/wp-json\/wp\/v2\/media\/56454"}],"wp:attachment":[{"href":"https:\/\/yilkomer.com\/en\/wp-json\/wp\/v2\/media?parent=56453"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/yilkomer.com\/en\/wp-json\/wp\/v2\/categories?post=56453"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/yilkomer.com\/en\/wp-json\/wp\/v2\/tags?post=56453"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}